Update Monday, March 17, 2025 at 9:30am
TSO is actively bringing the Klaus data center back online following the switch gear maintenance for the building this weekend.
There was an unplanned issue causing the data center to come back online Saturday evening. Fortunately, the spot coolers were keeping the data center cool. The data center began overheating on Sunday when the maintenance resumed Sunday morning causing the spot coolers to go offline. TSO staff was able to come onsite late Sunday afternoon to turn the UPS back off as the building's electrical maintenance was not complete. This has potentially caused issues with servers and TSO staff is actively troubleshooting.
Some services there were not originally slated to be impacted, but were are listed below:
www.cc.gatech.edu
ic.gatech.edu
scp.gatech.edu
cse.gatech.edu
scs.gatech.edu
sci.gatech.edu
support.cc.gatech.edu
grad.cc.gatech.edu
help.cc.gatech.edu
hr-help.cc.gatech.edu
===========================================================
WHAT’S HAPPENING?
KACB will have a full building power outage. A list of affected servers and services are below.
WHEN IS IT HAPPENING?
Starting at 5pm on March 14th, 2025, TSO will power down servers in KACB 2219 data center.
Switchgear maintenance will begin on Saturday, March 15th, and continue until completed on Sunday evening, March 16th.
TSO will begin powering up servers at 7am Monday, March 17th, and will provide a status update at 2pm.
WHY IS IT HAPPENING?
Routine switchgear maintenance for buildings occurs every five years.
WHO IS AFFECTED?
Occupants of KACB and all faculty, staff, and students with computers located in KACB or that use the following servers/services in the KACB 2219 data center.
Affected services:
Linux:
esperanto: classes.cc.gatech.edu, faculty.cc.gatech.edu, and sites.cc.gatech.edu
felix: Undergrad home directories hu23, hu24,hu25
holder: Faculty home directories
oscar: Grad student home directories hu19, hu20, hu21
transporter: DNS / NTP / YP Master
Windows:
cc-shemp: adminfs, winhome, and commshare
cc-larry: FileMakerPro - ccdb.cc.gatech.edu
cc-curly: Uniflow/Printing printer server
cc-trakaweb: Keybox Servers
Instructional:
PYNQ boards
Ultra boards
WHAT DO YOU NEED TO DO?
No user action is required. If you encounter issues following TSO's status update message at 2pm on Monday, March 17th, please reach out to the Help Desk for further assistance.
WHO SHOULD YOU CONTACT FOR QUESTIONS?
Feel free to contact the TSO Help Desk (CCB 225D, 404.894.7065, helpdesk@cc.gatech.edu).